Those aren’t supposed to be round on top.

  • rumba@lemmy.zipOP
    link
    fedilink
    English
    arrow-up
    7
    ·
    19 hours ago

    And to be completely honest, if you call an HVAC repair company, they’re likely to do a whole PM cycle on it. Flush the condensate line and pan, clean the coils and the heat exchanger, replace the contactor if you have one, take the temperature differential to make sure the unit is operating reasonably well, replace the blower belt it’s not direct drive. I PM the unit myself every spring and fall. I probably should have had eyes on that cap though.

    • Canonical_Warlock@lemmy.dbzer0.com
      link
      fedilink
      English
      arrow-up
      1
      ·
      edit-2
      2 minutes ago

      Yeah, testing caps is also a pretty regular part of our PM process. Especially because that one looks like it may partially be a run cap and a system can often run perfectly fine without a run cap except it will cause the motor to pull higher amps and run hotter. Catching a bad run cap early is the difference between replacing a bad cap and replacing a burned up motor.

      Edit: Although you’re already doing far more for your system than most. I’m an actual tech and it’s been a shamefully long time since my equipment at home has had a full PM done.